Calculation of Touch Voltage Based on Physical Distribution of Earth Fault Current

Calculation of Touch Voltage Based on Physical Distribution of Earth Fault Current

Authors :
Stevan Stanisic
Zoran Radakovic
Source :
IEEE Transactions on Power Delivery. 32:2246-2254
Publication Year :
2017
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2017.

Abstract

In this paper, the finite-elements method was used to analyze the approximation being typically used in the international standards for the calculation of the touch voltage, appearing at earth faults in power networks. The calculations in this paper were performed on the series of earthing systems applied in practice and the results are compared with the results of the widely accepted approximate method from standards. The origin of discrepancy in the results is analyzed and evaluated. The outcome of this paper is the justification of the application of Thevenin's theorem and the development of the higher accuracy equations for the resistance between feet and remote earth in case of the application of high resistivity additional surface material.