Analysis of the Performance of a GAX Hybrid (Solar - LPG) Absorption Refrigeration System Operating with Temperatures from Solar Heating Sources.
- Source :
- Energy Procedia; Dec2012, Vol. 30, p884-892, 9p
- Publication Year :
- 2012
-
Abstract
- Abstract: This paper presents the analysis of the experimental tests performed with an absorption refrigeration advanced Solar-GAX system, designed for 10.5kW (3 Ton) of cooling using ammonia-water mixture. The system designed for operation at heat source temperatures of around 200°C, consists of an absorber and generator of a falling film type and air cooled finned tube condenser and absorber, being an option for areas with water scarcity. Heat source temperatures of 160°C were established to simulate the conditions of using solar thermal concentrating technology to supply heat the system, this means the system operating at partial load. Cooling capacities from 3 to 7kW were obtained, with an average coefficient of performance (COP) of 0.37. Thermal stability was rapidly reached, after only 15minutes of operation. [Copyright &y& Elsevier]
Details
- Language :
- English
- ISSN :
- 18766102
- Volume :
- 30
- Database :
- Supplemental Index
- Journal :
- Energy Procedia
- Publication Type :
- Academic Journal
- Accession number :
- 84554779
- Full Text :
- https://doi.org/10.1016/j.egypro.2012.11.100