Back to Search Start Over

Detection of defects in on-load tap-changers using acoustic emission method.

Authors :
Cichon, Andrzej
Boczar, Tomasz
Fracz, Pawel
Zmarzly, Dariusz
Source :
2012 IEEE International Symposium on Electrical Insulation; 1/ 1/2012, p184-188, 5p
Publication Year :
2012

Abstract

The on-load tap changer (OLTC) constitutes one of the main elements of an energy power transformer which ensures the possibility of voltage regulation in an energy power net. Its break-down is a common cause for the transformer cut-off. The paper presents results of scientifically investigative works which aim is the OLTC technical condition estimation by use of the acoustic emission (AE) method. The AE method allows for OLTC diagnosis without the necessity of exclusion the power transformer from operation. The measurements were performed under laboratory conditions. The influence of the degree wear and tear of the OLTC head on the AE signal was evaluated. Gathered signals were analyzed within the time and time-frequency domains. Results analysis in the time domain was performed by use of the Hilbert transform. Furthermore the characteristic times for the particular runs were calculated. Evaluation of the time-frequency domain results was performed by use of short-time Fourier transform. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISBNs :
9781467304887
Database :
Complementary Index
Journal :
2012 IEEE International Symposium on Electrical Insulation
Publication Type :
Conference
Accession number :
86566572
Full Text :
https://doi.org/10.1109/ELINSL.2012.6251454