Back to Search
Start Over
Thermal degradation characteristics of oil-filled cable joint with extremely degraded tan δ oil.
- Source :
- Electrical Engineering in Japan; Jan2012, Vol. 178 Issue 1, p1-10, 8p
- Publication Year :
- 2012
-
Abstract
- Much of oil-filled (OF) cable has been used for a long time as 66- to 500-kV extrahigh-voltage cable. Sometimes we can see extremely degraded tan δ oil (several tens of percent of tan δ, for example) in joint boxes, etc. The values of tan δ calculated by a simple combination model of paper/oil show that the oil-impregnated paper with such a high tan δ oil likewise has an extremely high tan δ, which must result in thermal breakdown. However, such an event has not taken place up to the present in actually operated transmission lines. This fact suggests that some mechanism for the suppression of tan δ has acted in the paper insulation impregnated with degraded tan δ oil. Therefore, we investigated in detail the tan δ characteristics of paper impregnated with extremely high tan δ oil. In addition, based on the investigation results, we developed a method for simulation of heat generation by dielectric loss in an OF cable joint (which has degraded tan δ oil). © 2011 Wiley Periodicals, Inc. Electr Eng Jpn, 178(1): 1-10, 2012; Published online in Wiley Online Library (). DOI 10.1002/eej.21184 [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 04247760
- Volume :
- 178
- Issue :
- 1
- Database :
- Complementary Index
- Journal :
- Electrical Engineering in Japan
- Publication Type :
- Academic Journal
- Accession number :
- 65833789
- Full Text :