Back to Search
Start Over
The jump phenomena.
- Source :
- IEEE Industry Applications Magazine; Sep/Oct2008, Vol. 14 Issue 5, p53-59, 7p
- Publication Year :
- 2008
-
Abstract
- This investigative study examines an overvoltage incident that occurred during a routine scheduled maintenance operation on a 24.94 kV distribution network. With two phases remaining energized from a three-phase source, over- voltages were observed at the open-ended phase terminal of the underground cable, and the possible causes of overvoltage, such as switching transients, subharmonic oscillations, and ferroresonance, were investigated. [ABSTRACT FROM PUBLISHER]