Back to Search Start Over

Additional eddy current losses in transformer working at static VAr compensation station.

Authors :
Witczak, Pawel
Osinski, Piotr
Source :
International Journal of Applied Electromagnetics & Mechanics; 2024, Vol. 76 Issue 1/2, p35-46, 12p
Publication Year :
2024

Abstract

The article discusses the impact of reactive power load on additional power losses in a high-power transformer operating at a VAr static compensation station. The presence of an almost pure capacitive load on the secondary side together with the thyristor switches is the cause of high-frequency components in the phase currents. The additional effect of electrical resonance between the transformer inductance and the load capacitance is also taken into account. The analysis is achieved using a three-dimensional finite element approach. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
13835416
Volume :
76
Issue :
1/2
Database :
Complementary Index
Journal :
International Journal of Applied Electromagnetics & Mechanics
Publication Type :
Academic Journal
Accession number :
181231508
Full Text :
https://doi.org/10.3233/JAE-230202