Back to Search Start Over

Fault diagnosis for multiple current sensors in grid‐connected inverter based on average modulation voltage.

Authors :
Zhang, Fan
Zhang, Zhiwei
Jin, Guangfeng
Wang, Tianzhen
Han, Jingang
Razik, Hubert
Wang, Yide
Source :
IET Power Electronics (Wiley-Blackwell); Jan2024, Vol. 17 Issue 1, p54-66, 13p
Publication Year :
2024

Abstract

Grid‐connected inverters are the core equipment in the renewable power system. There are multiple current sensors which may affect the driving module of the switch in inverter. In multiple current sensor fault diagnosis, the coupling between fault components makes fault diagnosis difficult. This paper presents an offset fault diagnosis method of multiple current sensors based on the average modulation voltage model. Based on the influence of current sensor offset fault in the system, the average modulation voltage model is established in three‐phase stationary coordinates. The difference between the measured value of the current and the actual value is estimated through the model when the offset fault occurs. And then the fault is located. Experimental results show that the fault can be located accurately and fault tolerant control can be performed by this method when there are offset faults in multiple sensors simultaneously. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
17554535
Volume :
17
Issue :
1
Database :
Complementary Index
Journal :
IET Power Electronics (Wiley-Blackwell)
Publication Type :
Academic Journal
Accession number :
174563484
Full Text :
https://doi.org/10.1049/pel2.12614