Back to Search
Start Over
Characteristic Tests of a 1 MVA Single Phase HTS Transformer With Concentrically Arranged Windings.
- Source :
- IEEE Transactions on Applied Superconductivity; Jun2005 Part 2 of 3, Vol. 15 Issue 2, p2214-2217, 4p
- Publication Year :
- 2005
-
Abstract
- A 1 MVA single phase high temperature superconducting (HTS) transformer was manufactured and tested. The rated voltage of primary and secondary of HTS transformer are 22.9 kV and 6.6 kV respectively. BSCCO-2223 HTS tape was used for HTS windings of 1 MVA HTS transformer. In order to reduce AC loss generated in the HTS winding, the concentrically arranged winding was adopted to 1 MVA HTS transformer. Single HTS tape for primary windings and 4 parallel HTS tapes for secondary windings were used considering the each rated current of the HTS transformer. A core of HTS transformer was fabricated as a shell type core made of laminated silicon steel plate. And a GFRP cryostat with a room temperature bore was also manufactured. The characteristic tests such as no load test, short circuit test and several insulation tests were performed at 65 K using sub-cooled liquid nitrogen. Through these test results, the validity of design of HIS transformer was ascertained. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 10518223
- Volume :
- 15
- Issue :
- 2
- Database :
- Complementary Index
- Journal :
- IEEE Transactions on Applied Superconductivity
- Publication Type :
- Academic Journal
- Accession number :
- 17400190
- Full Text :
- https://doi.org/10.1109/TASC.2005.849615