Back to Search Start Over

Complete operational voltage assessment of Shandong pilot offshore wind project.

Authors :
Cai, Deyu
Liu, Xumin
Xu, Dapeng
Source :
Engineering Reports; Jan2023, Vol. 5 Issue 1, p1-15, 15p
Publication Year :
2023

Abstract

This article presents a thorough methodology for the voltage assessment of pilot offshore wind project in Shandong province, China. The results presented in this paper can be considered as the milestone of the offshore wind research in Shandong Province since there is still no grid codes for offshore wind power plant grid connection in the local electrical power grid. It mainly consists of three parts. In the first part, a detailed model of the offshore wind farm created in the DIgSILENT PowerFacotry simulation platform is presented, including wind turbines, power converters, transformers, submarine cables and relevant control schemes. In the second part, nonlinear time‐domain simulations were performed to analyze the wind farm's active power, reactive power, and voltage conditions under different wind scenarios. Based on the simulations results, a dynamic reactive power compensation system was proposed, and the consequence of the reactive power compensation was also demonstrated using nonlinear time‐domain simulations. [ABSTRACT FROM AUTHOR]