Back to Search
Start Over
Fault Ride Through of Inverter-Interfaced Renewable Energy Sources for Enhanced Resiliency and Grid Code Compliance.
- Source :
- IEEE Transactions on Sustainable Energy; Oct2022, Vol. 13 Issue 4, p2275-2290, 16p
- Publication Year :
- 2022
-
Abstract
- Inverter-interfaced renewable energy sources (IIRESs) are typically controlled during fault conditions to meet fault ride-through (FRT) requirements, e.g., reactive current generation (RCG) requirements specified by grid codes (GCs). However, fault currents generated by inverters are different from the traditional sources, i.e., synchronous generators. Consequently, phase selection methods (PSMs) used by protection relays could suffer from erroneous fault type classification. This paper develops a dual current controller (DCC) that regulates the inverter's negative- and positive-sequence currents to simultaneously meet phase selection and RCG requirements. First, the negative-sequence-current angle is obtained based on the angles of both zero- and positive-sequence currents to enable a correct operation for phase selection. Then, the positive-sequence current angle is adjusted to reach a trade-off between RCG requirements and phase selection achieved by the negative-sequence current. Lastly, the reference currents of the IIRES are generated in the stationary frame without violating the inverter's current limits. The proposed DCC supports the grid voltage by meeting the RCG requirements and enhancing the grid reliability and resilience by enabling correct phase selection. Comprehensive time-domain and real-time simulation verify the precise operation of the proposed DCC under various fault conditions and GCs. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 19493029
- Volume :
- 13
- Issue :
- 4
- Database :
- Complementary Index
- Journal :
- IEEE Transactions on Sustainable Energy
- Publication Type :
- Academic Journal
- Accession number :
- 160689840
- Full Text :
- https://doi.org/10.1109/TSTE.2022.3191631