Back to Search Start Over

A Three-Level Planning Model for Optimal Sizing of Networked Microgrids Considering a Trade-Off Between Resilience and Cost.

Authors :
Wang, Yi
Rousis, Anastasios Oulis
Strbac, Goran
Source :
IEEE Transactions on Power Systems; Nov2021, Vol. 36 Issue 6, p5657-5669, 13p
Publication Year :
2021

Abstract

Extreme events can cause severe power system damage. Resilience-driven operation of networked microgrids (MGs) has been heavily studied in literature. There is, though, little research considering the influence of resilience on decision making for planning. In this paper, a three-level model is suggested to solve the optimal sizing problem of networked MGs considering both resilience and cost. In the first level, a meta-heuristic technique based on an adaptive genetic algorithm (AGA) is utilized to tackle the normal sizing problem, while a time-coupled AC OPF is utilized to capture stability properties for accurate decision-making. The second and third levels are combined as a defender-attacker-defender model. In the former, the suggested AGA is utilized to generate attacking plans capturing load profile uncertainty and contingencies for load shedding maximization, while a multi-objective optimization problem is suggested for the latter to obtain a trade-off between cost and resilience. Simulations considering meshed networks and load distinction into critical and non-critical are developed to demonstrate algorithm effectiveness on capturing resilience at the planning stage and optimally sizing multiple parameters. The results indicate that higher resilience levels lead to higher investment cost, while sizing networked MGs leads to decreased investment in comparison with standalone MGs sizing. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858950
Volume :
36
Issue :
6
Database :
Complementary Index
Journal :
IEEE Transactions on Power Systems
Publication Type :
Academic Journal
Accession number :
153711531
Full Text :
https://doi.org/10.1109/TPWRS.2021.3076128