Back to Search
Start Over
Load frequency control by de‐loaded wind farm using the optimal fuzzy‐based PID droop controller.
- Source :
- IET Renewable Power Generation (Wiley-Blackwell); Jan2019, Vol. 13 Issue 1, p180-190, 11p
- Publication Year :
- 2019
-
Abstract
- In this study, the authors represent a modelling to analyse and simulate renewable power generation for two area power systems in the presence of high penetrated wind farm. The performance of assumed power systems may hazard without appropriate frequency amelioration methodologies. To complete the LFC model for two area power systems, the combination of automatic generation control and automatic voltage regulation of thermal units is considered. Due to the decline in the total inertia of power system associated with wind farm contribution, the self‐tuning and adaptive fuzzy‐based PID droop can be proposed in the structure of wind turbines instead of the fixed/traditional PID droop in de‐loaded area to ameliorate the frequency excursions. Besides, the artificial bee colony algorithm can tune the parameters of membership functions for input and output signals based on a multi‐objective function (MOF). The proposed strategy control is proved to be accurately stable under various load changes and yields more satisfactory performance in comparison to the conventional PID droop. This research generally includes wind farm collaboration in the frequency control by inertia, primary and secondary frequency control. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 17521416
- Volume :
- 13
- Issue :
- 1
- Database :
- Complementary Index
- Journal :
- IET Renewable Power Generation (Wiley-Blackwell)
- Publication Type :
- Academic Journal
- Accession number :
- 148143986
- Full Text :
- https://doi.org/10.1049/iet-rpg.2018.5392