Back to Search Start Over

Effect of BESS Response on Frequency and RoCoF During Underfrequency Transients.

Authors :
Brogan, Paul Vincent
Best, Robert J.
Morrow, D. John
McKinley, Kenneth
Kubik, Marek L.
Source :
IEEE Transactions on Power Systems; Jan2019, Vol. 34 Issue 1, p575-583, 9p
Publication Year :
2019

Abstract

Battery energy storage system (BESS) services will be of great help when operating power systems at high renewable energy penetrations. This paper demonstrates the requirements for effective frequency and inertia services. Some system operators currently apply scalars to financially reward improved performance. This paper demonstrates a method of validating and improving these scalars by considering the delay time and ramp time of the BESS. The importance of the method used to measure the rate of change of frequency is discussed in the paper. While the rate of change of frequency services improves with reduced delivery times, limits are identified where further reductions produce a negligible impact. This demonstrates the tangible benefits of a rapid response, and that current technology could meet the criteria. A variety of BESS capacities are trialed, which demonstrate consistency in performance and the occurrence of diminishing returns [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858950
Volume :
34
Issue :
1
Database :
Complementary Index
Journal :
IEEE Transactions on Power Systems
Publication Type :
Academic Journal
Accession number :
133690812
Full Text :
https://doi.org/10.1109/TPWRS.2018.2862147