Influence of the AMF Arc Control on Voltage Distribution of Double-Break VCBs.
- Source :
- IEEE Transactions on Plasma Science; Oct2016 Part 2, Vol. 44 Issue 10, Part 2, p2455-2461, 7p
- Publication Year :
- 2016
-
Abstract
- This paper investigates the influence of the axial magnetic field (AMF) arc control on voltage distribution (VD) of double-break vacuum circuit breakers (VCBs) in order to gain balanced VD, and thus enhance the breaking capacity. The interaction of vacuum arc plasma, postarc current (PAC), and AMF is discussed. We conduct the breaking test of double-break VCBs with externally applied AMF of a different pulsewidth, magnitude, and a different moment. The PAC, postarc charge, and the VD are measured to analyze the relationship between the AMF arc control and the VD. The optimal AMF arc control and the relationship between the AMF magnitude and the unbalanced voltage ratio are gained when the grading capacitors were 400 pF. The experimental test showed that the proper AMF arc control can improve the unbalanced VD. The mechanism is that the proper AMF arc control can make the postarc charge small and stable, so the unbalanced postarc charge, which caused the unbalanced VD is limited. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 00933813
- Volume :
- 44
- Issue :
- 10, Part 2
- Database :
- Complementary Index
- Journal :
- IEEE Transactions on Plasma Science
- Publication Type :
- Academic Journal
- Accession number :
- 118689610
- Full Text :
- https://doi.org/10.1109/TPS.2016.2603532