Back to Search Start Over

Reliable Generator Islanding Detection for Industrial Power Consumers With On-Site Generation.

Authors :
Anne, RadhaKiranMaye
Katha Basha, Faridul
Palaniappan, Ramanathan
Oliver, Kent L.
Thompson, Michael J.
Source :
IEEE Transactions on Industry Applications; Jan2016, Vol. 52 Issue 1, p668-676, 9p
Publication Year :
2016

Abstract

Large power consumers often have on-site generation. If the utility tie opens, it is essential to isolate the on-site generators to prevent generator equipment damage before the utility attempts to reclose in a possible out-of-synchronism condition. Typically, islanding detection schemes are used to detect this condition and disconnect on-site generation quickly, thereby allowing successful utility reclose. This paper introduces a reliable islanding detection solution that was proposed, implemented, and tested at a refinery in Texas. The facility houses two on-site generators and is interconnected to the utility via a looped system. A topology-based islanding detection scheme was originally installed at this facility but was later decommissioned because of difficulties in adapting to evolving topology changes. Following an undesirable event in the utility system that could have resulted in damage to the refinery on-site generator equipment, the refinery decided to implement an islanding detection scheme that is independent of system topology changes and only relies on local-area measurements. However, the dependability of a traditional local measurement-based scheme is vulnerable to the dynamic generation–load mismatch, making it possibly unreliable. This paper describes a solution using a redundant high-speed multiprinciple islanding detection scheme that incorporates a unique voting supervision logic to achieve security. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00939994
Volume :
52
Issue :
1
Database :
Complementary Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
112441535
Full Text :
https://doi.org/10.1109/TIA.2015.2466560