Back to Search Start Over

A Study on Transformer Loading in Manitoba—Peak-Load Ambient Temperature.

Authors :
Xin Li
Zielke, Garry
Source :
IEEE Transactions on Power Delivery; Oct2003, Vol. 18 Issue 4, p1249-1256, 8p, 2 Black and White Photographs, 1 Diagram, 7 Charts, 13 Graphs
Publication Year :
2003

Abstract

It is shown that the hourly ambient temperature and load of a substation transformer in Manitoba, observed over the three-month winter or summer time window, are governed by the normal distribution, respectively, and they jointly follow the bivariate normal distribution. Based on this, a rigorous model for the peak-load ambient temperature (i.e., the ambient temperature at the time when the winter or summer peak-load of the transformer occurs) is developed. This makes it possible to accurately determine the peak load capability of the transformer if its historical hourly ambient temperature and load data are available. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
18
Issue :
4
Database :
Complementary Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
11200369
Full Text :
https://doi.org/10.1109/TPWRD.2003.817734