Back to Search Start Over

Quantitative Risk Assessment of an Oil-Gas-Hydrogen-Electricity Integrated Energy Station in China.

Authors :
Zhao J
Wu M
Lu H
Li G
Xu Y
Tian M
Source :
ACS omega [ACS Omega] 2024 Sep 07; Vol. 9 (37), pp. 38887-38896. Date of Electronic Publication: 2024 Sep 07 (Print Publication: 2024).
Publication Year :
2024

Abstract

This paper presents a quantitative risk assessment (QRA) study of an oil-gas-hydrogen-electricity integrated energy station in China. A comprehensive assessment of the station was made in terms of consequences and risks, respectively. Consequence analysis shows that the severity of hazardous chemical leakage accidents in the station is in the order of natural gas, hydrogen, gasoline, and diesel fuel, especially in the liquefied natural gas (LNG) and compressed natural gas (CNG) storage tank areas, which may cause major accidents in the event of leakage. The results of the risk assessment showed that the individual and societal risks of the integrated oil-gas-hydrogen-electricity energy station exceeded the risk acceptance criteria. Moreover, the catastrophic rupture of LNG and CNG storage tanks is the main cause of the unacceptable risk. Additional mitigation measures for them, mainly including the installation of emergency manual shut-off valves, the installation of combustible gas detection and alarm devices, and pressure relief protection devices, can effectively reduce the risk to an acceptable level.<br />Competing Interests: The authors declare no competing financial interest.<br /> (© 2024 The Authors. Published by American Chemical Society.)

Details

Language :
English
ISSN :
2470-1343
Volume :
9
Issue :
37
Database :
MEDLINE
Journal :
ACS omega
Publication Type :
Academic Journal
Accession number :
39310211
Full Text :
https://doi.org/10.1021/acsomega.4c05050