Back to Search Start Over

Community-acquired Legionnaires' disease associated with a cooling tower: evidence for longer-distance transport of Legionella pneumophila.

Authors :
Addiss DG
Davis JP
LaVenture M
Wand PJ
Hutchinson MA
McKinney RM
Source :
American journal of epidemiology [Am J Epidemiol] 1989 Sep; Vol. 130 (3), pp. 557-68.
Publication Year :
1989

Abstract

In the period August 10-29, 1986, 29 confirmed cases of Legionnaires' disease occurred in Sheboygan, Wisconsin; two cases were fatal. No common source of indoor exposure was identified. Water specimens were obtained from all known cooling tower units in Sheboygan; Legionella pneumophila serogroup 1 was isolated at 1 x 10(6) colony-forming units per liter from a specimen obtained August 27 at plant A. This isolate was identical to the only clinical isolate by monoclonal antibody and isoenzyme subgrouping. Of 29 persons with Legionnaires' disease, 21 lived or worked within one mile (1.6 km) of plant A; seven of the remaining eight visited within one to two miles (1.6 to 3.2 km) of plant A from three to seven days before onset of illness. Attack rates were highest for persons living within 0.5 mile (0.8 km) of plant A. These findings associate a cooling tower with community-acquired Legionnaires' disease and suggest that dissemination of Legionella may occur over longer than previously recognized distances.

Details

Language :
English
ISSN :
0002-9262
Volume :
130
Issue :
3
Database :
MEDLINE
Journal :
American journal of epidemiology
Publication Type :
Academic Journal
Accession number :
2764000
Full Text :
https://doi.org/10.1093/oxfordjournals.aje.a115370