[Effect of ammonia-oxidizing bacteria (AOB) on chloraminated disinfection attenuation in drinking water distribution system].

Authors :
Bai XH
Cai YL
Zhou BH
Zhi XH
Source :
Huan jing ke xue= Huanjing kexue [Huan Jing Ke Xue] 2009 Jun 15; Vol. 30 (6), pp. 1649-52.
Publication Year :
2009

Abstract

The growth of microbe and formation of biofilm in water distribution system were important factors affecting the security of water quality. The number of ammonia-oxidizing bacteria (AOB) in biofilm of a chloraminated drinking water distribution system in Shanghai was detected by MPN-Griess method, and the relations among AOB, nitrification and chloraminated disinfection were analyzed. Meanwhile, the effects of AOB on chloraminated disinfection fastness and attenuation by simulation experiment were studied. The result indicated that the number of ammonia-oxidizing bacteria in pipe biofilm was between 1.0 x 10(2)-4.3 x 10(5) MPN/g dry biofilm. Correlation coefficients of AOB with ammonia, nitrite and nitrate were -0.563, 0.603 and -0.563. Correlation coefficients of AOB with total chlorine and mono-chloramine were -0.659 and -0.571. Fastness of AOB to chloramine was higher than heterotrophic bacteria and AOB can deplete more chloramine than HPC.