Reconstructing and tracking network state from a limited number of synchrophasor measurements.
- Source :
-
IEEE Transactions on Power Systems . May2013, Vol. 28 Issue 2, p1921-1929. 9p. - Publication Year :
- 2013
-
Abstract
- A method is proposed to reconstruct and track network state from a limited number of phasor measurement unit (PMU) data. To deal with the resulting unobservability, the state with bus powers and generator voltages closest to previously estimated values is computed. Those values, treated as pseudo-measurements, are obtained from the last reconstructed state, in a recursive manner. The method involves solving an optimization problem with linear constraints. It is scalable insofar as it accommodates from a few PMUs up to configurations ensuring full network observability. Reconstruction of only a region is possible. These and other features are demonstrated on the Nordic32 test system, with synchronized phasors obtained from detailed time simulation of a situation evolving towards instability. Suitable choices of PMU location and pseudo-measurements are also discussed. [ABSTRACT FROM PUBLISHER]
Details
- Language :
- English
- ISSN :
- 08858950
- Volume :
- 28
- Issue :
- 2
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Power Systems
- Publication Type :
- Academic Journal
- Accession number :
- 92680787
- Full Text :
- https://doi.org/10.1109/TPWRS.2012.2231439