Back to Search
Start Over
Procedures to Determine k-Factor Function for Air Gaps.
- Source :
-
IEEE Transactions on Power Delivery . Apr2013, Vol. 28 Issue 2, p686-692. 7p. - Publication Year :
- 2013
-
Abstract
- The new IEC 60060-1 standard establishes the k-factor function to determine the test voltage value of lightning impulses with superimposed oscillations, but no rule is given to determine experimental k-factor values. Testing methods, testing setups, and formulas to determine k-factor values are some crucial issues to obtain good results. This paper describes the two procedures used in the investigation funded by the European community and referenced in the Annex D of the last edition of IEC 60060-1 standard to determine experimental k-factor for air gaps, one for nonhomogenous fields and other for quasihomogenous fields. Both procedures were implemented using a setup with only 1 generator and a setup with 2 generators. Compatibility of new experimental k-factor values determined for air gaps up to 900 kV in quasihomogenous field with the factor function stated in IEC 60060-1 is shown by means of several examples, but additional examples show a significant discrepancy for air clearances of a sharp rod-plate configuration in the voltage range 250 to 800 kV. [ABSTRACT FROM PUBLISHER]
Details
- Language :
- English
- ISSN :
- 08858977
- Volume :
- 28
- Issue :
- 2
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Power Delivery
- Publication Type :
- Academic Journal
- Accession number :
- 86391361
- Full Text :
- https://doi.org/10.1109/TPWRD.2012.2228012