Current Transformer Saturation Effects on Coordinating Time Interval.

Authors :
Smith, Terrence
Hunt, Richard
Source :
IEEE Transactions on Industry Applications. Mar2013, Vol. 49 Issue 2, p825-831. 7p.
Publication Year :
2013

Abstract

The primary function of protective devices is to remove faulted equipment from the electrical system. It is typically very advantageous for these devices to isolate as small of a section of the electrical system as possible. Overcurrent protection is the most common protection function used, as faulted equipment typically results in a large short circuit current. When overcurrent protection is employed, the overcurrent protection is typically coordinated with time so that the devices closest to the fault will operate and isolate only that section of equipment before devices farther from the fault operate and isolate larger pieces of the system. These time overcurrent devices must also be coordinated with damage curves for equipment such as buses and cables to clear the fault before the overcurrent can cause damage to the equipment. This concept of time coordination of overcurrent is well understood, and there are general guidelines applied to account for measurement error and other inaccuracies. The reduced signal levels provided to relays due to current transformer (CT) saturation are normally not considered during coordination studies. This reduced signal level will result in slower than desired operation of protective relays. Feeder relays could trip slower than upstream devices, isolating more of the power system than intended, or could allow primary equipment to be damaged before tripping. This paper will review the concept of coordinating time overcurrent relays and then discuss the concept of loss of coordination associated with CT saturation. This paper will model CT saturation from actual installations using the IEEE Power System Relaying Committee CT Saturation Calculator tool. This model data will be used to estimate the performance of protective relays. This paper will discuss methods to improve the coordination of overcurrent relays when faced with significant CT saturation. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00939994
Volume :
49
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
86153339
Full Text :
https://doi.org/10.1109/TIA.2013.2243397