Back to Search Start Over

Experimental prediction of total thermal resistance of a closed loop EAHE for greenhouse cooling system

Authors :
Ozgener, Onder
Ozgener, Leyla
Goswami, D. Yogi
Source :
International Communications in Heat & Mass Transfer. Jul2011, Vol. 38 Issue 6, p711-716. 6p.
Publication Year :
2011

Abstract

Abstract: The design of an earth to air heat exchanger (EAHE) requires knowledge of its total thermal resistance (R Tot ) for heating and cooling applications. In this research, a 47m long horizontal, 56cm nominal diameter U-bend buried galvanized was studied experimental EAHE used for the determination and evaluation of thermal properties of heat exchanger. This system was designed and installed in the Solar Energy Institute, Ege University, Izmir, Turkey. Based on the experimental results, generalized relationships were developed for predicting of thermal resistance of the heat exchanger. Average total heat exchanger thermal resistance was estimated to be 0.021K-m/W as a constant value under steady state condition. [Copyright &y& Elsevier]