Model for Predicting DC Flashover Voltage of Pre-Contaminated and Ice-Covered Long Insulator Strings under Low Air Pressure.

Authors :
Jianlin Hu
Caixin Sun
Xingliang Jiang
Qing Yang
Zhijin Zhang
Lichun Shu
Source :
Energies (19961073). Apr2011, Vol. 4 Issue 4, p628-643. 16p. 1 Color Photograph, 4 Diagrams, 4 Charts.
Publication Year :
2011

Abstract

In the current study, a multi-arc predicting model for DC critical flashover voltage of iced and pre-contaminated long insulator strings under low atmospheric pressure is developed. The model is composed of a series of different polarity surface arcs, icicle-icicle air gap arcs, and residual layer resistance. The calculation method of the residual resistance of the ice layer under DC multi-arc condition is established. To validate the model, 7-unit and 15-unit insulator strings were tested in a multi-function artificial climate chamber under the coexistent conditions of low air pressure, pollution, and icing. The test results showed that the values calculated by the model satisfactorily agreed with those experimentally measured, with the errors within the range of 10%, validating the rationality of the model. [ABSTRACT FROM AUTHOR]