Back to Search Start Over

Comprehensive Adaptive Distance Relaying Scheme for Parallel Transmission Lines.

Authors :
Upendar, J.
Gupta, C. P.
Singh, G. K.
Source :
IEEE Transactions on Power Delivery. 04/01/2011, Vol. 26 Issue 2, p1039-1052. 14p.
Publication Year :
2011

Abstract

Reach accuracy of a distance relay is adversely affected by prefault system conditions, ground fault resistance, shunt capacitance, and mutual coupling of parallel lines. This paper presents a comprehensive adaptive relaying scheme for stand-alone distance protection of parallel transmission lines under a single-line-to-ground fault condition taking into account all of these factors. The proposed adaptive scheme is based on the back-propagation neural network used for training and adaptation. The relay acts as a stand-alone relay, which does not require a separate communication channel for real-time data transmission during faults. The simulation results show significant improvement in the relay selectivity. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
26
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
59569145