Back to Search
Start Over
Analysis of a Commercial Wind Farm in Taiwan Part II: Different Current-Limit Reactors and Load Tap Changers on System Performance.
- Source :
-
IEEE Transactions on Industry Applications . 03/01/2011, Vol. 47 Issue 2, p954-964. 11p. - Publication Year :
- 2011
-
Abstract
- This paper presents the effects of installing variable current-limit reactors (CLRs) and adjusting load tap changers (LTCs) on the performance of a commercial wind farm in Taiwan using computer simulations. The companion paper (Part I) demonstrates the field-measured results, simulation model, and simulation results of the studied Jang-Bin wind farm with 23 2-MW doubly fed induction generator-type wind turbine generators connected to the utility system through a 23/161-kV 60-MVA step-up main transformer (MT) from six feeders. Six CLRs, which were originally designed to limit short-circuit currents under faulted conditions, are connected in series with the six feeders. The LTCs of the MT are used to adjust/regulate the secondary-side voltage at the 23-kV bus. Some simulated steady-state and transient results of the studied wind farm with variable values of the proposed CLRs and LTCs are analyzed and compared. [ABSTRACT FROM PUBLISHER]
Details
- Language :
- English
- ISSN :
- 00939994
- Volume :
- 47
- Issue :
- 2
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Industry Applications
- Publication Type :
- Academic Journal
- Accession number :
- 59470768
- Full Text :
- https://doi.org/10.1109/TIA.2010.2091373