Back to Search Start Over

Influence of Low Atmospheric Pressure on AC Pollution Flashover Performance of Various Types of Insulators.

Authors :
Zhijin Zhang
Xinliang Jiang
Yafeng Chao
Caixin Sun
Jianlin Hu
Source :
IEEE Transactions on Dielectrics & Electrical Insulation. Apr2010, Vol. 17 Issue 2, p425-433. 9p.
Publication Year :
2010

Abstract

The electrical performance of outdoor insulators decreases under low air pressure conditions. The ac pollution flashover performance of various types of insulators are investigated in the multifunction artificial climate chamber in the State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University. The field investigation of the ac pollution flashover voltage performance are carried out at three different high altitudes including Wangkun station (altitude of 4484 m), Nachitai station (altitude of 3575 m) along the Qingzang railway and Geermu urban (altitude of 2820 m). The test results indicate that the characteristic exponent n describing the influence degree of air pressure on pollution flashover voltage, which has influence on the pollution flashover voltage of insulators, is variable, and the value of n is related to the pollution, insulator type etc. Under ac voltage, n is 0.45-0.85. The composite insulators are superior in external insulation selection in high altitude and heavy polluted areas. The relative error between the field test results and laboratory test results is less than 8 %, so the research results obtained in the laboratory can be applied to engineering design. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
10709878
Volume :
17
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Dielectrics & Electrical Insulation
Publication Type :
Academic Journal
Accession number :
50995190
Full Text :
https://doi.org/10.1109/TDEI.2010.5448097