Humidification of Large-Scale Cleanrooms by Adiabatic Humidification Method in Subtropical Areas: An Industrial Case Study.

Authors :
Chen, Jacky
Shih-Cheng Hu
Liang-Han Chien
Tsao, James J. M.
Tee Lin
Source :
ASHRAE Transactions. 2009, Vol. 115 Issue 2, p299-305. 7p.
Publication Year :
2009

Abstract

This study investigates the performance of adiabatic humidification in a large-scale cleanroom with various humidification methods. Theoretical analysis and experimental results show that adiabatic humidification is feasible. The relative humidity (RH) distribution in the cleanroom was within ±1% and the time variation of RH was within ±1% also, even when humidity of make-up air varies drastically. We found that adiabatic humidification with spray nozzles using "high-pressure water atomization" method is favorable than the "two-fluids humidification" method. The effect on energy-saving of adiabatic humidification and operational/initial cost of various humidification methods are also discussed. [ABSTRACT FROM AUTHOR]