Back to Search
Start Over
Effects of biofouling on air-side heat transfer and pressure drop for finned tube heat exchangers
- Source :
-
International Journal of Refrigeration . Aug2009, Vol. 32 Issue 5, p1032-1040. 9p. - Publication Year :
- 2009
-
Abstract
- Abstract: Experimental investigations on the effects of biofouling on air-side heat transfer and pressure drop for three biofouled finned tube heat exchangers and one clean finned tube heat exchanger were performed. Artificial accelerated method of microorganism growth on the fin surface was used for simulating the biofouled finned tube heat exchangers. Experimental results indicate that the effects of biofouling on the air-side heat transfer coefficient decreases 7.2% at 2.0m/s when the biofouled area ratio is 10%, while it decreases 15.9% at 2.0m/s when the biofouled area ratio is 60%, and biofouling causes a 21.8%∼41.3% increase in pressure drop when the air velocity is between 0.5 and 2.0m/s. The increase of inlet air velocity is helpful to improve the long-term performance of finned tube heat exchanger. Biofouling makes the hydrophilic coating failure, and the condensation water easily converges on the fin surface where biofouling grows. [Copyright &y& Elsevier]
Details
- Language :
- English
- ISSN :
- 01407007
- Volume :
- 32
- Issue :
- 5
- Database :
- Academic Search Index
- Journal :
- International Journal of Refrigeration
- Publication Type :
- Academic Journal
- Accession number :
- 41689684
- Full Text :
- https://doi.org/10.1016/j.ijrefrig.2008.10.007