Overvoltage Protection of Large Power Transformers A Real-Life Study Case.

Authors :
Bak, Claus Leth
Einarsdóttir, Kristin Erla
Andresson, Einar
Rasmussen, Jesper M.
Lykkegaard, Jan
Wiechowski, Wojciech
Source :
IEEE Transactions on Power Delivery. Apr2008, Vol. 23 Issue 2, p657-666. 10p. 9 Black and White Photographs, 9 Diagrams, 7 Charts, 10 Graphs.
Publication Year :
2008

Abstract

This paper demonstrates the results from a detailed study of the overvoltage protection of a particular 400/150-kV 400-MVA power transformer. The work presented here is based on a real-life power system substation design and data and initiated by Danish TSO Energinet.dk as a consequence of serious transformer overvoltag damage. A simulation model for the entire system consisting of overhead line, transformer, surge arrester, and earth grid has been created in PSCADIEMTDC. The main focus has been put on the earth grid, which has been submodeled in detail in MATLAB using an electromagnetic transient approach based on the thin-wire program made by J. H. Richmond for NASA in 1974. The earth grid model is verified with excellent agreement compared to already published results. The overvoltage performance of the particular case is analyzed, and it shows that the transformers LIWL have probably been exceeded. It is clearly illustrated that the transient performance of the earth grid plays an important role in the overall overvoltage protection system design. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
23
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
31647484
Full Text :
https://doi.org/10.1109/TPWRD.2007.905793