Back to Search
Start Over
Modified method of high alternating current measurement.
- Source :
-
IET Science, Measurement & Technology (Institution of Engineering & Technology) . May2008, Vol. 2 Issue 3, p107-113. 7p. 1 Diagram, 3 Graphs. - Publication Year :
- 2008
-
Abstract
- The conventional current transformers (CTs) in the form of a bar primary and secondary winding on a highly permeable ring core suffer from ratio error and phase angle errors, which are primarily due to the no-load current of the transformer. A modified design of a CT has been described. In this design, a feedback technique has been used in order to reduce the no-load current to a negligibly small value so that the said error may be minimal. Using this technique, a CT has been designed and fabricated with the commercially available material. The performance of the transformer has been tested experimentally and the output and input AC waves have been observed in a storage cathode ray oscilloscope (CRO) and the experimental results are reported. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 17518822
- Volume :
- 2
- Issue :
- 3
- Database :
- Academic Search Index
- Journal :
- IET Science, Measurement & Technology (Institution of Engineering & Technology)
- Publication Type :
- Academic Journal
- Accession number :
- 31229993
- Full Text :
- https://doi.org/10.1049/iet-smt:20070029