Back to Search Start Over

A simple instant-estimation method for time-average quantities of single-phase power and application to single-phase power grid connection by inverter.

Authors :
Shinnaka, Shinji
Source :
Electrical Engineering in Japan. Apr2007, Vol. 159 Issue 2, p34-43. 10p. 2 Diagrams, 5 Graphs.
Publication Year :
2007

Abstract

This paper presents and analyzes a new simple instant-estimation method for time-average quantities such as rms values of voltage and current, active and reactive powers, and power factor for single-phase power with the fundamental component of constant or nearly constant frequency by measuring instantaneous values of voltage and current. According to the analyses, the method can instantly estimate time-average values with accuracy of the fundamental frequency, and estimation accuracy of the power factor is about two times better than that of voltage, current, and powers. The instant-estimation method is simple and can be easily applied to single-phase power control systems that are expected to control instantly and continuously power factor on a single-phase grid by inverter. Based on the proposed instant-estimation method, two methods for such power control systems are also proposed and their usefulness is verified through simulations. © 2007 Wiley Periodicals, Inc. Electr Eng Jpn, 159(2): 34–43, 2007; Published online in Wiley InterScience (<URL>www.interscience.wiley.com</URL>). DOI 10.1002/eej.20236 [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
04247760
Volume :
159
Issue :
2
Database :
Academic Search Index
Journal :
Electrical Engineering in Japan
Publication Type :
Academic Journal
Accession number :
24192318
Full Text :
https://doi.org/10.1002/eej.20236