Measurement of AT Electric Railway System Currents at Power-Supply Frequency and Validation of a Multiconductor Transmission-Line Model.

Authors :
Celia, Roberto
Giangaspero, Giuseppe
Mariscotti, Andrea
Montepagano, Angelo
Pozzobon, Paoio
Ruscelli, Marco
Vanti, Maurizio
Source :
IEEE Transactions on Power Delivery. Jul2006, Vol. 21 Issue 3, p1721-1726. 6p. 5 Charts, 2 Graphs.
Publication Year :
2006

Abstract

An electric traction system supplied at 2 × 25 kV with autotransformers (ATs) is considered. The conductors' arrangement is that of the new European High Speed Railway Line (HSRL) under construction: The overhead supply conductors in contact with the train pantograph are connected to a symmetrical circuit (the feeder) with the purpose of current balancing; the traction return current flows from the rolling stock axles back to the supply (i.e., substation) through the traction rails and additional return conductors. The test campaign carried on the Rome-Naples HSRL allowed the validation of the multiconductor transmission line model used for system analysis. Measurements were performed in normal system configuration (2 × 25-kV supply) and degraded configuration (1 × 25 kV with AT and feeder not operating). Metrological issues (accuracy and consistency) are detailed for the presented results. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
21
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
21582771
Full Text :
https://doi.org/10.1109/TPWRD.2006.874109