CRDS‐based measurement of CO/CO2 concentration ratios for assessing transformer insulation aging.

Authors :
Wu, Yuxiang
Ma, Tiehua
Zhou, Yueting
Gong, Ting
Tian, Yali
Sun, Xiaocong
Guo, Guqing
Qiu, Xuanbing
Li, Chuanliang
Source :
Microwave & Optical Technology Letters. Oct2024, Vol. 66 Issue 10, p1-10. 10p.
Publication Year :
2024

Abstract

A gas analyzer has been developed using cavity ring‐down spectroscopy (CRDS) technology, designed to simultaneously measure the concentrations of CO2 and CO. These gases are critical indicators of transformer insulation degradation. The analyzer covers a CO2 concentration range from a few ppm to several thousand ppm and can measure CO/CO2 concentration ratios from 0.076 to 0.8. The selected absorption lines for CO and CO2 are centered at 6337.99 and 6338.59 cm−1, respectively. The two candidate lines are proximate to each other and nonoverlapping. The experimental results indicate that the system accurately fits the measured and calculated signals, enabling concentration measurements at the ppm level. This confirms its ability to measure the gas concentrations and ratios critical for assessing the condition of transformer insulation. This CRDS‐based system offers a reliable and sensitive method for early detection of potential transformer faults. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08952477
Volume :
66
Issue :
10
Database :
Academic Search Index
Journal :
Microwave & Optical Technology Letters
Publication Type :
Academic Journal
Accession number :
180522068
Full Text :
https://doi.org/10.1002/mop.70011