Back to Search Start Over

A Joint Active Damping Strategy Based on LCL -Type Grid-Connected Inverters for Grid Current Feedback and PCC Voltage Unit Feedforward.

Authors :
Ke, Shanwen
Liang, Bo
Source :
Sensors (14248220). Sep2024, Vol. 24 Issue 18, p6029. 18p.
Publication Year :
2024

Abstract

The negative high-pass filter feedback of the grid current (NFGCF) can offer active damping for the LCL-type grid-connected inverter. Due to the control delay in digital control systems, this damping can cause the system to exhibit non-minimum phase behavior within specific frequency ranges. This study proposes a joint active damping approach that combines grid current feedback and the point of common coupling (PCC) voltage unit feedforward. The proposed method introduces a dynamic damping region that varies with grid impedance. By developing suitable damping loop control parameters, this region can span the entire frequency range, even exceeding the Nyquist frequency fs/2. The research results demonstrate that the proposed approach enhances robustness against variations in grid impedance and eliminates non-minimum phase behavior. Simulation and experimental outcomes validate the effectiveness of this joint active damping method. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
14248220
Volume :
24
Issue :
18
Database :
Academic Search Index
Journal :
Sensors (14248220)
Publication Type :
Academic Journal
Accession number :
179964693
Full Text :
https://doi.org/10.3390/s24186029