Back to Search Start Over

Research on noise reduction methods for indoor substations based on resonant sound absorption.

Authors :
Jiangang Ma
Mingxin Geng
Yalin Zhao
Lv Wang
Chuang Fan
Jipu Guo
Xiaobing Yu
Source :
Vibroengineering Procedia. Apr2024, Vol. 54 Issue 1, p167-173. 7p.
Publication Year :
2024

Abstract

Aiming to reduce the impact of substation noise on the lives of surrounding residents, improving the low and middle frequencies acoustic performance of traditional resistive mufflers in indoor substations is significant. The paper is based on the resonance sound absorption mechanism, and for the first time applies multi-frequency resonance noise reduction technology to the research field of indoor substation noise control, proposing a multi-frequency resonant muffling structure. The acoustic performance of the proposed muffler unit is investigated through theoretical and numerical analysis. The measured noise data of the indoor substation is used as sound excitation in the numerical analysis. The results show that at frequencies of 100 Hz, 200 Hz, 300 Hz, 400 Hz, and 500 Hz, the noise in indoor substations is significantly reduced by the multi-frequency resonant muffling structure. The paper provides references for the application of multi-frequency resonant mufflers in the field of noise control of indoor substations. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
23450533
Volume :
54
Issue :
1
Database :
Academic Search Index
Journal :
Vibroengineering Procedia
Publication Type :
Academic Journal
Accession number :
176731894
Full Text :
https://doi.org/10.21595/vp.2024.24080