Comparing two topology transformer hysteresis models derived from DC hysteresis measurements.

Authors :
Albert, Dennis
Domenig, Lukas Daniel
Schachinger, Philipp
Roppert, Klaus
Renner, Herwig
Source :
COMPEL. 2023, Vol. 42 Issue 4, p861-877. 17p.
Publication Year :
2023

Abstract

Purpose: The purpose of this paper is to investigate the applicability of a direct current (DC) hysteresis measurement on power transformer terminals for the subsequent hysteresis model parametrization in transformer grey box topology models. Design/methodology/approach: Two transformer topology models with two different hysteresis models are used together with a DC hysteresis measurement via the power transformer terminals to parameterize the hysteresis models by means of an optimization. The calculated current waveform with the derived model in the transformer no-load condition is compared to the measured no-load current waveforms to validate the model. Findings: The proposed DC hysteresis measurement via the power transformer terminals is suitable to parametrize two hysteresis models implemented in transformer topology models to calculate the no-load current waveforms. Originality/value: Different approaches for the measurement and utilization of transformer terminal measurements for the hysteresis model parametrization are discussed in literature. The transformer topology models, derived with the presented approach, are able to reproduce the transformer no-load current waveform with acceptable accuracy. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
03321649
Volume :
42
Issue :
4
Database :
Academic Search Index
Journal :
COMPEL
Publication Type :
Periodical
Accession number :
164398276
Full Text :
https://doi.org/10.1108/COMPEL-09-2022-0303