Back to Search Start Over

Influence of twisted tape length on the thermal performance of a heat exchanger tube.

Authors :
Panda, Jyoti Prakash
Kumar, Bipin
Kumar, Manoj
Patil, Anil Kumar
Source :
Numerical Heat Transfer: Part A -- Applications. 2023, Vol. 83 Issue 6, p650-663. 14p.
Publication Year :
2023

Abstract

The application of twisted tape inserts in heat exchangers allows higher heat transfer rates with a simultaneous loss of energy due to turbulence and friction. In a conventional approach, the twisted tape is placed in the entire length of the heat exchanger. The present study explores the effect of the length of the twisted tape insert at a different twist ratio (TR) for 4700 < Re < 22,800. The insert length ratio (LR) ranges from 0.25 to 1 and the TR ranges from 1.5 to 6. The maximum Nusselt number corresponds to the LR of 0.75 at a TR of 1.5. The maximum thermo-hydraulic performance is found to be 3.2 for the LR of 0.75 at a TR of 1.5. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
10407782
Volume :
83
Issue :
6
Database :
Academic Search Index
Journal :
Numerical Heat Transfer: Part A -- Applications
Publication Type :
Academic Journal
Accession number :
161895792
Full Text :
https://doi.org/10.1080/10407782.2022.2102341