The energy and time saving coordinated control methods of CO2, VOCs, and PM2.5 in office buildings.

Authors :
Wu, Xiaochun
Zhang, Yan
Hou, Fang
Wang, Huichao
Zhou, Jianjie
Yu, Wei
Source :
PLoS ONE. 9/27/2022, Vol. 17 Issue 9, p1-19. 19p.
Publication Year :
2022

Abstract

Indoor air pollution is complex and serious. In fact, an on-site investigation of an office building revealed that the concentration of three typical pollutants (CO2, VOCs, PM2.5) exceeded the Chinese standard. To identify a better control method to achieve good indoor air quality, an orthogonal experiment was carried out in an environmental chamber to compare the control time and energy consumption of four control methods (purifier+ and window+, purifier+ and window-, purified fresh air 240 m3/h and purified fresh air 400 m3/h) to meet the standard established for pollutants. The purifier+ and window+ method was found to be more effective in most conditions, with a control time reduced by 8.06% and energy consumption reduced by 11.91% compared with the traditional control method of purified fresh air 240 m3/h. This research highlights the optimal control strategy for the air quality in office buildings under different pollution conditions. [ABSTRACT FROM AUTHOR]