Back to Search Start Over

System Vulnerability Analysis Simulation Model for Substation Subjected to Earthquakes.

Authors :
Liang, Huangbin
Xie, Qiang
Source :
IEEE Transactions on Power Delivery. Aug2022, Vol. 37 Issue 4, p2684-2692. 9p.
Publication Year :
2022

Abstract

To evaluate the earthquake-resistance capability of an entire substation, which is a complex multi-input-multi-output system (MIMOS) composed of many various types of electrical equipment interconnected by conductors, a flow-based analysis model integrating the merit of the flow block diagram and state tree method was introduced. Two performance indicators of a substation were defined from different stakeholders, one is the expected total power transmission capacity and the other is the power accessibility to the targeted users from the substation. And directed graph logic system analysis models were developed on the Simulink platform based on the original internal logic relationship among distributed components and the power delivery path in the substation with different function types. Afterward, the defined reliability indicators associated with the overall system under a certain seismic intensity level can be obtained by combining the seismic vulnerability curve at the equipment level through the Monte Carlo simulation method. The feasibility and accuracy of the proposed system vulnerability analysis model were verified by comparison with the analytical solution through the illustrative simple MIMOS. Then A case study on a practical 220/110 kV substation was conducted, the analysis results can assist decision-makers in seismic optimization of different retrofitting measures and distribution plans for substations. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
37
Issue :
4
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
158186363
Full Text :
https://doi.org/10.1109/TPWRD.2021.3114279