Back to Search Start Over

Reduction Measures of the Overvoltage in the TN System of a Building Struck Directly by Lightning.

Authors :
Yasui, Shinji
Komori, Shunya
Yamamoto, Tatsuya
Kobayashi, Hiroshi
Source :
IEEE Transactions on Electromagnetic Compatibility. Dec2021, Vol. 63 Issue 6, p2024-2032. 9p.
Publication Year :
2021

Abstract

To protect the equipment in a building struck directly by lightning, surge protective devices (SPDs) are installed between the neutral line and ground lines at the power utility substation of a TT system. In this case, when operating the SPD, the wiring system of the low-voltage distribution line will be a TN system. Although the overvoltage between these lines at the power utility substation can be limited during SPD operation, an overvoltage between these lines is induced at each floor distribution board connected thereafter. Here, we analyzed this overvoltage in the VSTL electromagnetic analysis software. The overvoltage was found to largely depend on the loop impedance of the wirings as the lightning current flowed from the structure to the protective ground line. The most effective solution was separating the ground lines from the power supply lines connected to the distribution boards of each floor with another electric pipe shaft. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00189375
Volume :
63
Issue :
6
Database :
Academic Search Index
Journal :
IEEE Transactions on Electromagnetic Compatibility
Publication Type :
Academic Journal
Accession number :
154149218
Full Text :
https://doi.org/10.1109/TEMC.2021.3102976