Estimation Method of Voltage Sag Frequency Considering Transformer Energization.
- Source :
-
IEEE Transactions on Power Delivery . Dec2021, Vol. 36 Issue 6, p3404-3413. 10p. - Publication Year :
- 2021
-
Abstract
- The inrush current generated by power transformer energization (TE) causes voltage sag of the nearby bus, the typical residual voltage of the voltage sag caused by transformer energization (VSTE) is about 0.7 p.u.--0.9 p.u. and lasts for a longer duration, which may lead to the sensitive equipment trips. This paper proposes an estimation method of voltage sag frequency considering VSTE. Firstly, based on the maximum entropy method, the residual flux distribution is calculated by considering the relationship between the residual flux and closing angle at the moment of TE. The voltage sag waveform caused by TE is calculated based on the estimation of the probability distribution of residual flux, to evaluate VSTE objectively and comprehensively. Secondly, this paper proposes a non-rectangular voltage sag equivalent frequency statistical method based on multiple magnitude-duration (MMD) function, to avoid the overestimation of voltage sag frequency by the traditional methods. Furthermore, this paper proposes an assessment algorithm of voltage sag frequency. Finally, the simulation of IEEE-30 test system verifies the necessity and correctness of the proposed method. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 08858977
- Volume :
- 36
- Issue :
- 6
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Power Delivery
- Publication Type :
- Academic Journal
- Accession number :
- 153854283
- Full Text :
- https://doi.org/10.1109/TPWRD.2020.3041000