Optimal Sizing of Energy Station in the Multienergy System Integrated With Data Center.

Authors :
Lyu, Jiawei
Zhang, Shenxi
Cheng, Haozhong
Yuan, Kai
Song, Yi
Fang, Sidun
Source :
IEEE Transactions on Industry Applications. Mar/Apr2021, Vol. 57 Issue 2, p1222-1234. 13p.
Publication Year :
2021

Abstract

This article proposes a novel optimal sizing method for the energy station in the multienergy system (MES) integrated with data center. First, an overall framework of the energy station, data center, and multienergy loads is constructed to describe the interconnection of energy system and information system. Then, the dynamic voltage frequency scaling (DVFS) technique, the thermal inertia, and the deep coupling relationships of the electricity load, waste heat, cooling load, and workload in the data center are respectively modeled. On this basis, the optimal sizing model of the energy station is established, in which the data center can participate in the integrated demand response by the DVFS technique and thermal inertia. The capacity of energy station and the scheduling schemes of energy devices and servers are optimized simultaneously to coordinate the energy flow and information flow. Based on the quasi-steady-state assumption of thermal balance, the model is simplified to a mixed-integer quadratic program problem, and it is solved by Gurobi. Case studies based on a real-world test system in China illustrate that the integration of data center can be utilized to reduce the total cost of energy station planning in MES. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00939994
Volume :
57
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
149510195
Full Text :
https://doi.org/10.1109/TIA.2021.3054607