Experimental Analysis of an Air Heat Pump for Heating Service Using a "Hardware-In-The-Loop" System.

Authors :
Conti, Paolo
Bartoli, Carlo
Franco, Alessandro
Testi, Daniele
Source :
Energies (19961073). Sep2020, Vol. 13 Issue 17, p4498. 1p.
Publication Year :
2020

Abstract

Estimating and optimizing the dynamic performance of a heat pump system coupled to a building is a paramount yet complex task, especially under intermittent conditions. This paper presents the "hardware-in-the-loop" experimental campaign of an air-source heat pump serving a typical dwelling in Pisa (Italy). The experimental apparatus uses real pieces of equipment, together with a thermal load emulator controlled by a full energy dynamic simulation of the considered building. Real weather data are continuously collected and used to run the simulation. The experimental campaign was performed from November 2019 to February 2020, measuring the system performances under real climate and load dynamics. With a water set point equal to 40 °C, the average heat pump coefficient of performance was about 3, while the overall building-plant performance was around 2. The deviation between the two performance indexes can be ascribed to the continuous on-off signals given by the zone thermostat due to the oversized capacity of the heat emission system. The overall performance raised to 2.5 thanks to a smoother operation obtained with reduced supply temperature (35 °C) and fan coil speed. The paper demonstrates the relevance of a dynamic analysis of the building-HVAC system and the potential of the "hardware-in-the-loop" approach in assessing actual part-load heat pump performances with respect to the standard stationary methodology. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
19961073
Volume :
13
Issue :
17
Database :
Academic Search Index
Journal :
Energies (19961073)
Publication Type :
Academic Journal
Accession number :
145987788
Full Text :
https://doi.org/10.3390/en13174498