The reactive power demand in DEMO: Estimations and study of mitigation via a novel design approach for base converters.
- Source :
-
Fusion Engineering & Design . Sep2019:Part B, Vol. 146, p2687-2691. 5p. - Publication Year :
- 2019
-
Abstract
- In the present pre-conceptual design, the base converters to supply the main DEMO poloidal magnets are rated for 45 kA and about 10 kV. If the traditional design approach, based on thyristor bridges, was adopted, this would result in very large reactive power exchanged when low voltage values are required by the load. To satisfy the limitations imposed by National Grid Operators, the reactive power should be compensated inside the DEMO Plant Electrical System by means of a Reactive Power Compensation and Harmonic Filtering system. This could represent an additional cost and takes up a large area of the plant. This paper shows that the reactive power demand, estimated with an analytical model starting from the current/voltage waveforms foreseen in DEMO magnets, is huge. Therefore, an innovative approach, based on Active Front End converters, is proposed and compared with the traditional solution for coil power supplies. [ABSTRACT FROM AUTHOR]