Back to Search Start Over

Preventing maloperation of distance protection due to CCVT transients.

Authors :
Ahmadi, Seyed-Alireza
Sanaye-Pasand, Majid
Davarpanah, Mahdi
Source :
IET Generation, Transmission & Distribution (Wiley-Blackwell). 2019, Vol. 13 Issue 13, p2828-2835. 8p. 1 Black and White Photograph, 2 Diagrams, 2 Charts, 6 Graphs.
Publication Year :
2019

Abstract

Unsecured operation of backup distance relay during an external fault results in removing a needed energy link and can jeopardise overall system stability. This problem that is well known as distance relay overreach is very likely during coupling capacitor voltage transformer (CCVT) transients mainly under high system impedance ratio (SIR) conditions. To tackle this challenging problem, a new methodology consisting of three stages is proposed in this study. It is capable of solving the overreaching problem which occurs under high SIR conditions, without sacrificing the operation speed of distance relay for inside the first zone faults. Comprehensive simulation studies are carried out to test the proposed methodology. The obtained results demonstrate its feasibility and effectiveness for practical applications in the power system. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
17518687
Volume :
13
Issue :
13
Database :
Academic Search Index
Journal :
IET Generation, Transmission & Distribution (Wiley-Blackwell)
Publication Type :
Academic Journal
Accession number :
137387210
Full Text :
https://doi.org/10.1049/iet-gtd.2018.6559