Back to Search Start Over

SEQUENTIAL LOOP CLOSING IDENTIFICATION OF MULTIVARIABLE PROCESSES USING THE BIASED RELAY FEEDBACK METHOD.

Authors :
KOO, DOEGYOON
PARK, HOCHEOL
CHOI, JINYOUNG
LEE, JIETAE
Source :
Chemical Engineering Communications. May2004, Vol. 191 Issue 5, p611-624. 14p.
Publication Year :
2004

Abstract

Each controller in multiloop control systems for multivariable processes can be tuned sequentially with the ultimate information for the paired input and output while former loops have been closed, and hence, single-input single- output autotuning methods can be applied. In this sequential autotuning for multiloop control systems, several iterations are usually required for better control performances. Especially when pairings are undesirable, the auto- tuning sequences should be repeated with correct pairings, which result in long field experiments. Here, to avoid this drawback, a simple method to identify process models while loops are being sequentially tuned is proposed. The identified models can be used to correct pairings of multiloop control systems and to improve tuning performances without several field iterations. In addition, they can be used to obtain model-based control systems such as decoupling control systems. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00986445
Volume :
191
Issue :
5
Database :
Academic Search Index
Journal :
Chemical Engineering Communications
Publication Type :
Academic Journal
Accession number :
12887238
Full Text :
https://doi.org/10.1080/00986440490424574