Reliability assessment of slender concrete columns at the stability failure.
- Source :
-
AIP Conference Proceedings . 2017, p1-7. 7p. - Publication Year :
- 2017
-
Abstract
- The European Standard for designing concrete columns within the use of non-linear methods shows deficiencies in terms of global reliability, in case that the concrete columns fail by the loss of stability. The buckling failure is a brittle failure which occurs without warning and the probability of its formation depends on the columns slenderness. Experiments with slender concrete columns were carried out in cooperation with STRABAG Bratislava LTD in Central Laboratory of Faculty of Civil Engineering SUT in Bratislava. The following article aims to compare the global reliability of slender concrete columns with slenderness of 90 and higher. The columns were designed according to methods offered by EN 1992-1-1 [1]. The mentioned experiments were used as basis for deterministic nonlinear modelling of the columns and subsequent the probabilistic evaluation of structural response variability. Final results may be utilized as thresholds for loading of produced structural elements and they aim to present probabilistic design as less conservative compared to classic partial safety factor based design and alternative ECOV method. [ABSTRACT FROM AUTHOR]
- Subjects :
- *CONCRETE columns
*CONCRETE construction
*STANDARDS
*BRITTLENESS
*FRACTURE mechanics
Subjects
Details
- Language :
- English
- ISSN :
- 0094243X
- Database :
- Academic Search Index
- Journal :
- AIP Conference Proceedings
- Publication Type :
- Conference
- Accession number :
- 127293590
- Full Text :
- https://doi.org/10.1063/1.5019140