Back to Search Start Over

Disturbance Elimination for Partial Discharge Detection in the Spacer of Gas-Insulated Switchgears.

Authors :
Guoming Wang
Gyung-Suk Kil
Hong-Keun Ji
Jong-Hyuk Lee
Source :
Energies (19961073). Nov2017, Vol. 10 Issue 11, p1762. 12p.
Publication Year :
2017

Abstract

With the increasing demand for precise condition monitoring and diagnosis of gas-insulated switchgears (GISs), it has become a challenge to improve the detection sensitivity of partial discharge (PD) induced in the GIS spacer. This paper deals with the elimination of the capacitive component from the phase-resolved partial discharge (PRPD) signal generated in GIS spacers based on discrete wavelet transform (WT). Three types of typical insulation defects were simulated using PD cells. The single PD pulses were detected and were further used to determine the optimal mother wavelet. As a result, the bior6.8 was selected to decompose the PD signal into 8 levels and the signal energy at each level was calculated. The decomposed components related with capacitive disturbance were discarded, whereas those associated with PD were de-noised by a threshold and a thresholding function. Finally, the PRPD signals were reconstructed using the de-noised components. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
19961073
Volume :
10
Issue :
11
Database :
Academic Search Index
Journal :
Energies (19961073)
Publication Type :
Academic Journal
Accession number :
126447795
Full Text :
https://doi.org/10.3390/en10111762