Investigation on the adaptivity of the transcritical CO2 refrigeration system with a capillary.
- Source :
-
International Journal of Refrigeration . Jul2017, Vol. 79, p183-195. 13p. - Publication Year :
- 2017
-
Abstract
- In order to research the adaptivity of the capillary tube in the transcritical CO 2 refrigeration system, a separated flow model of a CO 2 capillary in which the metastable phenomenon was taken into consideration was built in the simulation of transcritical CO 2 refrigeration system, and related experiments were carried out by a plant under different gas-cooler outlet temperatures. The performances of the capillary based system were further compared with that of the EEV (electronic expansion valve) based system. The results showed that the relative COP ranged from 82% to 98% when there was a 10 °C deviation between the real gas-cooler outlet temperature and the design value. Thus the capillary based transcritical CO 2 system is promising and could achieve performance close to that of EEV based system in a wide range of gas-cooler outlet temperature. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 01407007
- Volume :
- 79
- Database :
- Academic Search Index
- Journal :
- International Journal of Refrigeration
- Publication Type :
- Academic Journal
- Accession number :
- 123428640
- Full Text :
- https://doi.org/10.1016/j.ijrefrig.2017.04.013